I/o complex equipment ‘sx7480, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual
Page 55

Trusted
TM
TMR Module T8160
Issue 13 May 13
PD-T8160
55
4.33. I/O Complex Equipment ‘SX7480’
Description:
T7480 Guarded Analogue Output Module. The Guarded Analogue Output Module
provides six 4mA - 20mA current output sources for driving user loads. The outputs
are 12-bit D-to-A converted values driven from a triplicated I/O Safetybus interface.
The module requires external power from a nominal 24V dc field power source to
power the optically isolated analogue field-side circuits. This board definition is for a
simplex configuration.
Product Description reference: PD-T7026 Guarded Analogue Output module
OEM PARAMETERS:
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed
REGENT_CHASSIS
REGENT_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O where the
Module is placed.
CONFIGURATION
PHYSICAL MODULE:
RACK 1:
6 ANALOGUE outputs
States to be written to the two modules identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 6 is module channel 6.
RACK 2:
1 BOOLEAN inputs
Module status.
FALSE – board ok, TRUE - board fault
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.