4.38. I/O Complex Equipment ‘SX7484’
Description:
T7484 Simplex Monitored Guarded Digital Output Module, 110V ac. The Monitored
Guarded Output Module provides switching of 90V ac to 130V ac power to 16 field
outputs. The outputs are arranged in two groups of 8 outputs, where each group is
powered from a common power source. This board definition is for a simplex
configuration.
Product Description reference: PD-T7033 Monitored Guarded Output Modules
OEM PARAMETERS
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed
REGENT_CHASSIS
REGENT_SLOT
1 - 16
1 - 10
The chassis & slot number within the Regent+Plus I/O where
the Module is placed.
MONITER_MASK
1 = mask fault LEDs
0 = enable fault LEDs
Module fault LED mask. Entered as a 16 bit word. Bit 0 will
mask channel 1,bit 15 will mask channel 16. This field will
mask the implementation of the fault LEDs on the module.
Input status is not affected.
FREQUENCY
0 - 1
Frequency of the module.
0 – 60Hz, 1 – 50Hz.
CONFIGURATION
PHYSICAL MODULE:
RACK 1:
16 BOOLEAN outputs
States to be written to the module identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 16 is module channel 16.
TRUE – channel high, FALSE – channel low
RACK 2:
16 BOOLEAN inputs
Inputs reflecting the channel status of the module specified.
Bit 0 is the state of Channel 1, Bit 15 is the state of Channel 16.
FALSE – channel ok, TRUE – channel fault
RACK 3:
1 BOOLEAN input
Input reflecting the board status of the module specified
FALSE – board ok, TRUE - board fault
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.