4.34. I/O Complex Equipment ‘SX7481’
Description:
T7481 Monitored Guarded Output Module, 24V dc. The Monitored Guarded Output
Module provides switching of 18V dc to 36V dc power to 16 field outputs. The outputs
are arranged in two groups of 8 outputs, where each group is powered from a common
power source. This board definition is for a simplex configuration.
Product Description reference: PD-T7033 Monitored Guarded Output Modules
OEM PARAMETERS:
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed
REGENT_CHASSIS
REGENT_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O where
the Module is placed.
MONITER_MASK
1 = mask fault LEDs
0 = enable fault LEDs
Module fault LED mask. Entered as a 16 bit word. Bit 0 will
mask channel 1,bit 15 will mask channel 16. This field will
mask the implementation of the fault LEDs on the module.
Input status is not affected.
FREQUENCY
0 – 1
Frequency of the module.
0 – 60Hz, 1 – 50Hz.
CONFIGURATION
PHYSICAL MODULE:
RACK 1:
16 BOOLEAN outputs
States to be written to the module identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 16 is module channel 16.
TRUE – channel high FALSE – channel low
RACK 2:
1 INTEGER input
Inputs reflecting the channel status of the module specified. Bit 0 is the
state of module channel 1, bit 15 is the state of module channel 16. 0 –
channel ok, 1 – channel fault
RACK 3:
1 BOOLEAN input
Input reflecting the board status of the module specified.
FALSE – board ok, TRUE - board fault.
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.