I/o complex equipment ‘sx7420a, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual
Page 37
![background image](/manuals/581210/37/background.png)
Trusted
TM
TMR Module T8160
Issue 13 May 13
PD-T8160
37
4.15. I/O Complex Equipment ‘SX7420A’
Description:
T7420A Analogue Input Module. The Analogue Input module provides high noise
immunity analogue to digital conversion of 8 differential or 16 single-ended field input
voltages or currents. The digitally converted values are interfaced to the triplicated I/O
Safetybus. This board definition is used in a simplex configuration for single-ended
inputs.
Product Description reference: PD-T7023 Analogue Input Modules
OEM PARAMETERS:
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed
REGENT_CHASSIS
REGENT_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O where the
Module is placed.
CONFIGURATION
PHYSICAL MODULE
RACK 1:
16 ANALOGUE Inputs
Input channel states of module identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 16 is module channel 16.
RACK 2:
16 BOOLEAN Inputs
Channel range status. Channel 1 is module channel 1, Channel 16 is
module channel 16.
TRUE = channel is in range, FALSE = channel out of range.
RACK 3:
16 BOOLEAN Inputs
Channel power status. Channel 1 is module channel 1, Channel 16 is
module channel 16.
TRUE = channel OK, FALSE = channel fault.
RACK 4:
1 BOOLEAN input
Module status. TRUE = Board fail, FALSE = board OK.
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.