I/o complex equipment ‘sx7488, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual
Page 66
Trusted
TM
TMR Module T8160
Issue 13 May 13
PD-T8160
66
4.44. I/O Complex Equipment ‘SX7488’
Description:
T7488 Monitored Guarded Digital Output Module, 120V dc. The Monitored Guarded
Output Module provides switching of 90V ac to 130V dc power to 16 field outputs. The
outputs are arranged in two groups of 8 outputs, where each group is powered from a
common power source. This board definition is for a simplex module configuration.
OEM PARAMETERS
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed
REGENT_CHASSIS
REGENT_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O
where the first Module is placed.
MONITER_MASK
1 = mask fault LEDs
0 = enable fault LEDs
First module fault LED mask. Entered as a 16 bit word.
Bit 0 will mask channel 1,bit 15 will mask channel 16. This
field will mask the implementation of the fault LEDs on the
module. Input status is not affected.
FREQUENCY
0 – 1
Frequency of the module.
0 – 60Hz, 1 - 50Hz.
CONFIGURATION
PHYSICAL MODULE:
RACK 1:
16 BOOLEAN outputs
States to be written to the module identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 16 is module channel 16.
TRUE – channel high, FALSE – channel low
RACK 2:
16 BOOLEAN inputs
Inputs reflecting the channel status of module specified. Channel 1 is the
state of module channel 1, Channel 16 is the state of module channel 16.
FALSE – channel ok, TRUE – channel fault
RACK 3:
16 BOOLEAN inputs
Inputs reflecting the board status of the module specified.
FALSE – board ok, TRUE – board fault
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.