I/o complex equipment ‘sx7418f, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual
Page 33

Trusted
TM
TMR Module T8160
Issue 13 May 13
PD-T8160
33
4.13. I/O Complex Equipment ‘SX7418F’
Description:
T7418F Monitored Digital Input Module, 120V ac/dc. The Monitored Digital Input
Module interfaces to 16 field input devices. The Type F module connects to field
inputs that switch the ‘hot’ side of field power ranging from 90 to 150V ac/dc. The
module performs complete testing of the input module electronics. This board
definition is used in a simplex configuration.
Product Description reference: PD-T7031 Monitored Digital Input Modules
OEM PARAMETERS:
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed
REGENT_CHASSIS
REGENT_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O
where the Module is placed.
MONITOR_MASK
1 = mask fault LEDs
0 = enable fault LEDs
Entered as a 16 bit word. Bit 0 will mask channel 1,bit 15 will
mask channel 16. This field will mask the implementation of
the fault LEDs on the module. Input status is not affected.
OPEN_VOLTAGE
0 – 240
Voltage at which to indicate failure at switch open. The data
is entered in the form of a decimal number in the range 0 -
255. However, 240 is the maximum the user can enter to
accommodate test ranges within the module.
ON_OFF_VOLTAGE
0 – 240
Voltage at which to indicate a transition from Low/High or
High/Low has taken place. It is again entered as a decimal
value the range 0 - 255. However, 240 is the maximum the
user can enter to accommodate test ranges within the
module.
SHORT_VOLTAGE
0 – 240
Voltage at which to indicate failure at switch close. The data
is entered in the form of a decimal number in the range 0 -
255, however 240 is the maximum the user can enter to
accommodate test ranges within the module.