Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual
Page 17
![background image](/manuals/581210/17/background.png)
Trusted
TM
TMR Module T8160
Issue 13 May 13
PD-T8160
17
EXTRA INFORMATION
TMR Interface Status word format
Bit No.
Description
State
0
TMR Interface Slice A status
See TMR Interface Slice status information.
1
TMR Interface Slice A status
See TMR Interface Slice status information.
2
TMR Interface Slice B status
See TMR Interface Slice status information.
3
TMR Interface Slice B status
See TMR Interface Slice status information.
4
TMR Interface Slice C status
See TMR Interface Slice status information.
5
TMR Interface Slice C status
See TMR Interface Slice status information.
6
Not Used
7
Not Used
8
Not Used
9
Not Used
10
Not Used
11
Active/Standby
0 – Standby, 1 - Active
12
Educated
0 – uneducated, 1 - educated.
13
Impending Module
0 – ejectors open, 1 - ejectors closed
14
Module online
0 – TMR Interface offline, 1 - TMR Interface online
15
Permissible Slot
0 – Invalid Slot, 1 - Permitted
TMR Interface Slice status information.
Bit n+1
Bit n
State
0
0
Healthy slice
0
1
Transient fault
1
0
Hard fault
1
1
Unknown
Transceiver variable
Each of the 16 variables has the following configuration
Transceiver A
bits 0,1
Transceiver B
bits 2,3
Transceiver C
bits 4,5
Bit n+1
Bit n
State
0
0
Transceiver Healthy
0
1
Transceiver transient fault
1
0
Transceiver hard fault
1
1
Unknown
Notes:
1. All parameters must be supplied, even for virtual boards.
2. This module must appear before any attached Regent modules in the rack list.
3. The Permissible Slot status bit is 1 when the TMR Interface module has been correctly
configured in the I/O Connections and in the System Configuration Tool, even if the module is
not present.
4. If the Module On-line status bit is zero, the other status bits should not be used.