4.22. I/O Complex Equipment ‘SX7441A’
Description:
T7441A Digital Output Module, 24V dc. The Digital Output Module provides digitally
switched outputs for controlling 16 field loads. The 24V dc digital output circuits are
‘sourcing’ outputs that switch field power ranging from 18V dc to 32V dc. Field power
for the outputs is arranged in two isolated groups of 8 points. This board definition is
used in a simplex configuration.
Product Description reference: PD-T7015 DC Digital Output Module
OEM PARAMETERS:
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed
REGENT_CHASSIS
REGENT_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O where the
Module is placed.
CONFIGURATION
PHYSICAL MODULE:
RACK 1:
16 BOOLEAN outputs
States to be written to the two modules identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 16 is module channel 16.
TRUE - channel high, FALSE – channel low
RACK 2:
1 BOOLEAN input
Input reflecting the board status of the two modules specified. FALSE -
board ok, TRUE – board fault
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.