I/o complex equipment ‘sx7481_p, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual
Page 59
Trusted
TM
TMR Module T8160
Issue 13 May 13
PD-T8160
59
4.37. I/O Complex Equipment ‘SX7481_P’
Description:
T7481 Monitored Guarded Output Module, 24V dc. The Monitored Guarded Output
Module provides switching of 18V dc to 36V dc power to 16 field outputs. The outputs
are arranged in two groups of 8 outputs, where each group is powered from a common
power source. This board definition is for a simplex configuration, has packed channel
status’ for each board and is recommended for use with medium to high output count
systems.
Product Description reference: PD-T7033 Monitored Guarded Output Modules
OEM PARAMETERS
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed
REGENT_CHASSIS
REGENT_SLOT
1 - 16
1 - 10
The chassis & slot number within the Regent+Plus I/O where the
Module is placed.
MONITER_MASK
1 = mask fault LEDs
0 = enable fault
LEDs
Module fault LED mask. Entered as a 16 bit word. Bit 0 will
mask channel 1,bit 15 will mask channel 16. This field will mask
the implementation of the fault LEDs on the module. Input
status is not affected.
FREQUENCY
0 - 1
Frequency of the module.
0 - 60Hz, 1 - 50Hz.
CONFIGURATION
PHYSICAL MODULE:
RACK 1:
16 BOOLEAN outputs
States to be written to the module identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 16 is module channel 16.
TRUE – channel high, FALSE – channel low
RACK 2:
1 ANALOGUE input
Input reflecting the channel status of the module specified.
Bit 0 is the state of Channel 1, Bit 15 is the state of Channel 16
0 - channel ok, 1 – channel fault
RACK 3:
1 BOOLEAN input
Input reflecting the board status of the module specified.
FALSE – board ok, TRUE - board fault
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.