4.26. I/O Complex Equipment ‘DX7446’
Description:
T7446 Relay Output Module. The Relay Output Module provides relay outputs for
controlling eight field loads. This board definition is used in a dual configuration. Each
module can be located in any Regent rack or slot.
Product Description reference: PD-T7017 Relay Output Module
OEM PARAMETERS:
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed
REGENT_CHASSIS
REGENT_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O where the
Module is placed.
PARTNER_CHASSIS
PARTNER_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O where the
Module is placed.
CONFIGURATION
PHYSICAL MODULE:
RACK 1:
8 BOOLEAN outputs
States to be written to the two modules identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 8 is module channel 8.
TRUE - channel high, FALSE – channel low
RACK 2:
2 BOOLEAN inputs
Input reflecting the board status of the two modules specified.
Channel 1 is the state of the first module. Channel 2 is the state of the
second.
FALSE - board ok, TRUE – board fault
PROGRAMMING NOTE
Writing to a channel of board 1 will cause physical writes to be made to both boards as identified by the
parameters associated with the board. Both boards must be managed by the same TMR Interface
module.
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.