Isolation, I/o modules supported – Rockwell Automation T8160 Trusted TMR Interface User Manual
Page 14

Trusted
TM
TMR Module T8160
Issue 13 May 13
PD-T8160
14
3.3. Isolation
All signals exchanged between fault containment regions are protected to prevent the propagation of
faults between independently powered regions.
The processor and front-panel interface fault containment regions provide isolation for the 24Vdc
power feed in addition to the POWER WARNING signal.
3.4. I/O Modules Supported
The T8160 interface provides the following support for the Regent+Plus I/O modules. The equivalent
Regent I/O modules are also supported since their I/O safetybus interface is identical.
Module
Single module
Dual set Triple set
3401/7401
Yes
Yes
3402/7402
Yes Yes
3404/7404
Yes
Yes
3408/7408
No support
3411/7411
Yes
3411F/7411F
Yes
Yes
3418F/7418F
Yes
3419/7419
Yes
3420A/7420A
Yes
3420AF/7420AF Yes – see below
3431/7431
Yes
3431A/431A
Yes
3432/7432
Yes – see below
3441A/7441A
Yes
Yes
3444/7444
Yes
Yes
3446H/7446H
Yes
Yes
3446L/7446L
Yes
Yes
3454/7454
No support
3461A/7461A
Yes Yes
3462A/7462A
Yes Yes
3464/7464
Yes
Yes
3468A/7468A
No support
3470A/7470A
Yes
3478/7480
Yes
3481/7481
Yes
Yes
3481A/7481A
Yes
Yes
3484/7484
Yes
Yes
3485/485
Yes
Yes
3488/7488
Yes
Yes
3488A/7488A
Yes
Yes
3491/7491
Yes
The 3420AF/420AF and 3432/7432 are not supported in Toolset / processor firmware TÜV 3.5.1. They
have since been added. Contact [email protected] for details if these modules are required.