4.40. I/O Complex Equipment ‘DX7484’
Description:
T7484 Simplex Monitored Guarded Digital Output Module, 110V ac. The Monitored
Guarded Output Module provides switching of 90V ac to 130V ac power to 16 field
outputs. The outputs are arranged in two groups of 8 outputs, where each group is
powered from a common power source. This board definition is for a dual module
configuration.
Product Description reference: PD-T7033 Monitored Guarded Output Modules
OEM PARAMETERS
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed
REGENT_CHASSIS
REGENT_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O
where the first Module is placed.
PARTNER_CHASSIS
PARTNER_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O
where the second Module is placed
MONITER_MASK
1 = mask fault LEDs
0 = enable fault LEDs
First module fault LED mask. Entered as a 16 bit word.
Bit 0 will mask channel 1,bit 15 will mask channel 16. This
field will mask the implementation of the fault LEDs on the
module. Input status is not affected.
FREQUENCY
0 – 1
Frequency of the module.
0 – 60Hz, 1 - 50Hz.
CONFIGURATION
PHYSICAL MODULE:
RACK 1:
16 BOOLEAN outputs
States to be written to the two modules identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 16 is module channel 16.
TRUE - channel high, FALSE - channel low
RACK 2:
16 BOOLEAN inputs
Inputs reflecting the channel status of first module of the two modules
specified. Channel 1 is the state of module channel 1, Channel 16 is the
state of module channel 16.
FALSE - channel ok, TRUE – channel fault
RACK 3:
16 BOOLEAN inputs
Inputs reflecting the channel status of second module of the two modules
specified. Channel 1 is the state of module channel 1, Channel 16 is the
state of module channel 16.
FALSE – channel ok, TRUE – channel fault
RACK 4:
2 BOOLEAN inputs
Inputs reflecting the board of the two modules specified. Channel 1 is the
state of the first module, Channel 2 is the state of the second.
FALSE - board ok, TRUE – board fault
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.
EXTRA INFORMATION
Writing to a channel of board 1 will cause physical writes to be made to both boards as identified by the
parameters associated with the board. Both boards must be managed by the same TMR Interface.