I/o complex equipment ‘sx7431a, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual
Page 41
Trusted
TM
TMR Module T8160
Issue 13 May 13
PD-T8160
41
4.19. I/O Complex Equipment ‘SX7431A’
Description:
T7431 Thermocouple Input Equipment. The thermocouple input equipment includes
a termination panel/multiplexer assembly and an input module that plugs into, and
interfaces with, a triplicated I/O Safetybus. The termination panel/multiplexer provides
connection points for 24 thermocouples and is cabled to the plug-in module. The
plug-in module provides 24 channel high noise immunity analogue to digital
conversion. This board definition is used in a simplex configuration. Input data is
unscaled.
Product Description reference: PD-T7024 Thermocouple Input Assembly
OEM PARAMETERS:
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed.
REGENT_CHASSIS
REGENT_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O where the
Module is placed.
CONFIGURATION
PHYSICAL MODULE:
RACK 1:
24 ANALOGUE Inputs
Input channel states of module identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 24 is module channel 24.
RACK 2:
24 BOOLEAN Inputs
Channel range status. Channel 1 is module channel 1, Channel 24 is
module channel 24.
TRUE = channel is in range, FALSE = channel out of range.
RACK 3:
1 BOOLEAN input
Module status.
TRUE = Board fail, FALSE = board OK.
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.