4.28. I/O Complex Equipment ‘DX7461’
Description:
T7461 DC Guarded Digital Output Module 24VDC. The DC Guarded Digital Output
Module provides digitally switched outputs for controlling eight field loads. Field power
for the outputs is arranged in two triplicated inputs. This board definition is used in a
dual configuration. . Each module can be in any Regent rack or slot. All data attached
to this definition is unpacked with BOOLEAN variables used.
Product Description reference: PD-7019 Regent+ Guarded 24, 48, 120Vdc.
OEM PARAMETERS:
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed
REGENT_CHASSIS
REGENT_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O where the
Module is placed.
PARTNER_CHASSIS
PARTNER_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O where the
Module is placed.
CONFIGURATION
PHYSICAL MODULE:
RACK 1:
8 BOOLEAN outputs
States to be written to the two modules identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 8 is module channel 8.
TRUE - channel high, FALSE – channel low
RACK 2:
2 BOOLEAN inputs
Input reflecting the board status of the two modules specified.
Channel 1 is the state of the first module. Channel 2 is the state of the
second.
FALSE - board ok, TRUE – board fault
PROGRAMMING NOTE
Writing to a channel of board 1 will cause physical writes to be made to both boards as identified by the
parameters associated with the board. Both boards must be managed by the same TMR Interface
module.
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.