Relay parameters – Rockwell Automation 1440-PK02-05M2 XM-720 Machine Monitor User Manual
Page 48

Publication GMSI10-UM001C-EN-E - June 2011
48 Configuring the XM-720
Relay Parameters
Use the Alarm, Relay and 4-20 mA Output tab in the Configuration Tool to
configure the behavior of the relays in the XM-720 monitor.
In the provided configuration files, the relays are configured to function as
described in Table 3.4.
Refer to Files to Use With Your XM-720 Monitor on page 39 for a list of the
provided configuration files.
Table 3.4 Pre-Configured Relay Functionality
IMPORTANT
Making a change to the relay parameters may possibly
change the intended function of the relay and front panel
LED.
Configuration Tool
Relay Number
Front Panel
LED
Back Panel
Connection
Intended Function
1
Module Fault
N/A
Indicates a module fault, such as a hardware or
firmware failure.
Turns on the Module Fault LED on the front panel.
2
Xducer Fault
N/A
Indicates transducer DC bias on either channel is
out-of-range.
Turns on the Xducer Fault LED on the front panel.
3
N/A
Fault Relay
Indicates a module fault and/or transducer DC bias is
out-of-range.
4
Warning
Warning
Relay
Indicates that the overall measurement in either
channel exceeds either the alert level thresholds or the
danger level thresholds.
Turns on the Warning LED on the front panel.
5
Trip
Trip Relay
Indicates that the measurement in either channel
exceeds the danger level thresholds.
Turns on the Trip LED on the front panel.