Figure 2.11 non-contact sensor wiring important, Important – Rockwell Automation 1440-PK02-05M2 XM-720 Machine Monitor User Manual
Page 24
Publication GMSI10-UM001C-EN-E - June 2011
24 Installing the XM-720 Machine Monitor
Figure 2.11 Non-Contact Sensor Wiring
IMPORTANT
Using the XM Serial Configuration Utility, make certain the
IEPE Power parameter is disabled. Refer to Transducer
Parameters on page 44.
IMPORTANT
A jumper from terminal 5 to 21 on the XM-120/121/122
terminal block is required for channel 1 buffered output. A
jumper from terminal 22 to 21 on XM-120/121/122
terminal block is required for channel 2 buffered output.
Refer to Setting the Buffer Range for the Transducer on
page 20.
TYPICAL WIRING FOR NON-CONTACT SENSOR
TO XM-720 BACK PANEL
COM
SIG
-24
Shield
Floating
17
18
19
20
21
22
24
Signal Common
Channel 2 Input Signal
Shield
-24V DC
COM
SIG
-24
Shield
Floating
24
Channel 1 Input Signal
Signal Common
Shield
-24V DC