Connecting a non-contact sensor – Rockwell Automation 1440-PK02-05M2 XM-720 Machine Monitor User Manual
Page 23
Publication GMSI10-UM001C-EN-E - June 2011
Installing the XM-720 Machine Monitor 23
Figure 2.10 IEPE Accelerometer Wiring
Connecting a Non-Contact Sensor
The figure below show the wiring of a non-contact sensor to the XM-720 back
panel.
TYPICAL WIRING FOR IEPE ACCELEROMETER
TO XM-720 BACK PANEL
Shield
Channel 1 Input Signal
Signal Common
Shield
Channel 2 Input Signal
17
18
19
20
21
22
Signal Common
Pin A - Si gnal
Pin B - Common
Cable shield not
connected at this end
Pin A - Si gnal
Pin B - Common
Cable shield not
connected at this end
IMPORTANT
You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended
practice is to ground the cable shield to one of the Chassis
GND terminals on the XM-720 terminal block and not at
the transducer. Any of the Chassis GND terminals on the
XM-720 terminal block provides a grounding point for the
cable shield.
IMPORTANT
The internal transducer power supply is providing power to
the IEPE accelerometer.