Editing the xm-720 parameters, Transducer parameters – Rockwell Automation 1440-PK02-05M2 XM-720 Machine Monitor User Manual
Page 44

Publication GMSI10-UM001C-EN-E - June 2011
44 Configuring the XM-720
Editing the XM-720
Parameters
Once you open one of the provided configuration files, you can modify the
existing parameters so they better meet your requirements.
Transducer Parameters
The Channel tab in the Configuration Tool allows you to change the
characteristics of the transducers you will be using with your XM-720 monitor
as well as the signal processing performed on channel 1 or channel 2. There
are two Channel tabs, one for each channel.
In the provided configuration files, both channels are configured identically.
Refer to Files to Use With Your XM-720 Monitor on page 39 for a list of the
provided configuration files.
To modify the channel parameters, follow these steps.
1. In the XM Module Configuration Tool, click the appropriate Channel
tab. (Channel 1 is the default tab.) You will see a screen similar to this.
IMPORTANT
Any configuration parameter changes that you make in the
Configuration Tool do not affect the XM module until you
download them to the module. To download the
configuration parameters to the module, choose Device >
Download to Device. The module begins using the new
parameters immediately after the download.
Check this checkbox when an
IEPE accelerometer is wired to
the channel. Uncheck this
checkbox when any other type
of transducer is wired to the
channel.
A voltage reading outside this
range constitutes a transducer
fault.
The XM-122 can only perform
gSE measurements with an
accelerometer. gSE
measurements are only
available for this channel if you
select g.