Input / output modules, Replacement fuses, I/o module board options – Rockwell Automation 2755 Enhanced Decoder Series B User Manual
Page 26
2–9
Decoder Features
Publication 2755-833
Input/Output Modules
The optional I/O Module Board supports the following I/O modules:
Output Modules (function as a switch not a power source)
Catalog Number
2755-OB5S
2755-OA5S
2755-OM5S
Nominal Line Voltage
––
120 VAC
240 VAC
Maximum Line Voltage
60 VDC
140 VAC
280 VAC
Minimum Line Voltage
3.0 VDC
12 VAC
24 VAC
Maximum Peak Off State Voltage
60 VDC
400 V peak
600 V peak
Maximum Peak Off State Leakage
1.0 mA
2.5 mA RMS
4.5 mA RMS
Static off-state dv/dt
––
200 V/usec
200 V/usec
Maximum On-State Current
0.5 A DC
0.5 A RMS
0.5 A RMS
Minimum On-State Current
10 mA DC
50mA RMS
50mA RMS
Maximum 1 Cycle Surge
––
4.0 A peak
4.0 A peak
Maximum 1 Second Surge
1.5 A DC
––
––
Peak On-State Voltage
1.5 V DC
1.6 V peak
1.6 V peak
Input Modules (require voltage source for activation)
Catalog Number
2755-IB5S
2755-IA5S
①
2755-IM5S
①
Maximum Input Voltage
32 VDC
140V RMS/VDC
280V RMS/VDC
Minimum Input Voltage
3.3 VDC
90V RMS/VDC
180V RMS/VDC
Input Resistance
1 k ohm
–
–
Maximum Input Current
32mA DC @32VDC
10mA RMS @140V RMS
8mA RMS @280V RMS
Drop Out Current
1.0 mA DC
2.5 mA RMS
1.5 mA RMS
Allowable Off-State Input Current
1.0 mA DC
3.0 mA RMS
2.0 mA RMS
Allowable Off-State Input Voltage
2.0 VDC
50 VRMS/VDC
120 VRMS/VDC
①
AC or DC Input Module
Replacement Fuses
(for decoders with I/O Module Board options)
Replacement
Number
Description
77104-899-01
1.6 A plug-in fuse for output modules provide overload protection for decoder.
I/O Module Board Options
(available when ordering either the NEMA Type
1 or Type 4 decoder)
Module
Output Modules
Input Module
I/O Connector/
Option
I/O Board
Qty
Positions
Type
Qty
Position
Type
Cables
①
-B1
Yes
0
––
––
0
––
––
None
-B2
Yes
2
1, 2
3 - 60 VDC at 0.5 amps
1
8
3.3 - 32 VDC
None
-B5
Yes
0
––
––
0
––
––
1 set
-B6
Yes
0
––
––
0
––
––
2 sets
-B7
Yes
2
1, 2
3 - 60 VDC at 0.5 amps
1
8
3.3 - 32 VDC
2 sets
①
The I/O connector(s) wire to modules in positions 1-8 of the I/O board and comply with NEMA
Type 4 standards. Six foot (1.83 meter) cables are supplied with each connector for wiring to the
modules.