Bar graph register format selections – Rockwell Automation 2707-NP DTAM Programming Software User Manual
Page 94

Chapter 11
Creating Bar Graph Screens
11–6
The screen for a 16 Bit Signed Integer register is shown below. The screen
for a 16 Bit BCD register is similar.
SLC or PLC
depending upon protocol.
Format Selection
Description
Register Number
The controller address to be monitored.
Digits Right of Decimal
The number of digits to be placed to the right of the decimal.
Digits Left of Decimal
The number of digits to be placed to the left of the decimal.
Leave Place for Sign (Y or N)
Provides for a one character place for the polarity sign (+ or -) when
the data is displayed, if desired.
Minimum Register Value
The minimum data value of the controller address.
Maximum Register Value
The maximum data value of the controller address.
Minimum Displayed Value
The minimum data value to be displayed. This value is displayed
when the data in the controller address is equal to the minimum
register value.
Maximum Displayed Value
The maximum data value to be displayed. This value is displayed
when the data in the controller address is equal to the maximum
register value.
The range defined by the Minimum Displayed Value and the
Maximum Displayed Value is proportionally scaled to the range of
the minimum and maximum register values. If both ranges are equal
then the scaling ratio is 1:1.
Minimum Bar Value
The minimum value of data to be displayed in the bar graph. This
value must be greater or equal to the Minimum Displayed Value.
Maximum Bar Value
The maximum value of data to be displayed in the bar graph. This
value must be less than or equal to the Maximum Displayed Value
The minimum and maximum bar graph values may be used to
display a particular range or window of an overall range (Minimum
and Maximum Displayed Values).
Bar Graph Register
Format Selections