Connect external wiring – Rockwell Automation 1798-IB4 FlexArmor User Manual User Manual
Page 13

Publication 1798-UM001B-EN-P - November 2002
Install Your DeviceNet Adapter Module 1-5
3. Repeat steps 1 and 2 for each I/O module for the remaining
Baseplate I/O slots.
4. Screw down the module retaining screws to ensure IP67
compliance.
Connect External Wiring
Connect external wiring to the DeviceNet Field Termination Plug
(DFTP) as shown below.
1. Connect the DeviceNet cable to the DFTP as shown.
2. Insert the connector into the mating connector on the
3. DeviceNet FTP module.
IMPORTANT
I/O modules can be installed in any slot location to
the right of the adapter module. The adapter is
capable of addressing eight modules.
IMPORTANT
•
Torque the screws to 0.5-0.7 Nm. (4.43-6.2 inch
pounds).
•
Dust caps on the I/O modules must have 4 inch
pounds of torque to maintain IP67 compliance.
Connect
Connector Pin
To
BLK Wire
3
-V
BLU Wire
5
CAN* Low
Base Wire
1
Drain
WHT Wire
4
CAN High
RED Wire
2
+V
*CAN=Controller Area Network
42538
Micro Male connector (In)
1
2
3
4
5
1
2
3
4
5
Micro Female connector
(Daisy Chain Out)
1
2
3
4
5
1
2
3
4
5
Mini Male connector (In)
Mini Female connector
(Daisy Chain Out)
42653
DFTP1
DFTP2