Floor anchoring, Installation of power bus bushings, Floor anchoring installation of power bus bushings – Rockwell Automation 7763 OneGear MV SMC Flex Solid-State Motor Controller User Manual
Page 23

Rockwell Automation Publication 7760-IN001
B-EN-P - June 2013
21
Equipment Installation
Chapter 3
Floor Anchoring
The general location of the converter cabinet floor anchoring points is shown in
.
Refer to project specific dimension drawing for exact dimensions and anchoring
bolt mounting locations for all cabinets. Anchor holes accommodate 12 mm
(0.50”) hardware.
Figure 18 - Floor Anchoring
Installation of Power Bus
Bushings
Move bushing against the side sheet of the adjacent switchgear cabinet, as
illustrated in
. Align holes in bushing with holes in switchgear cabinet
and fasten using the supplied M8 hardware. This is typical for both sides.
SMC Floor
Anchoring
Adjacent Switchgear Cabinets
IMPORTANT
This step is only necessary if the installation procedure outlined in
, (i.e. if the horizontal power bus bushings have been
inserted onto the horizontal power bus and currently reside loose on the bus
inside the converter cabinet’s main bus box.)