Rockwell Automation 1794-OB16D FLEX I/O Diagnostic Modules User Manual User Manual
Page 37
Publication 1794-UM061A-EN-P - July 2006
Configuring Modules for Communication on a Remote I/O Network
35
4. Configure the 1756-DHRIO module parameters.
1756-DHRIO Module Properties Dialog Box
In This Field:
Do the Following:
Name
Type a name for the module (i.e.,DHRIO_module_in_slot_1).
Slot
Type or select the slot number where the module is installed.
Type
Channel A
Channel B
Select RIO for the Channel that is connected to the remote I/O network. If only one channel is configured as
a remote I/O scanner, we recommend that you use Channel B. If you configure Channel A as a remote I/O
scanner, you cannot use the programming terminal din connector on the front of the 1756-DHRIO module.
Baud Rate
Specify a baud rate for the Remote I/O channel. This value defines the communication rate at which the
1756-DHRIO module scans the remote I/O modules.
Revision
Select the major and minor revision level for your module.
Electronic Keying
Specify a keying option.
When you configure a module, you specify the slot number for the module. However, it is possible to place a
different module in that slot, either on purpose or accidently. Electronic keying lets you protect your system
against accidental placement of the wrong module in a slot. The keying option you choose determines how
closely a module in a slot must match the configuration for that slot.
Open Module Properties
Ensure that this box is checked to access all of the available configuration screens for the module. If this box
is not checked, clicking OK assigns the default parameters for the remaining configuration fields.
A. Define the following parameters:
• Name
• Slot
• Type
• Baud Rate
• Revision
• Electronic Keying
• Open Module Properties
Refer to the 1756-DHRIO Module
Properties Dialog Box table for
information on how to fill-in the dialog
box.
Click OK.
If:
Then Select:
all of the following must match:
• type
• catalog number
• vendor
• major and minor revision
number
Exact Match
all information except the minor
revision number must match
Compatible Module
no information must match
Disable Keying