Network compatibility, 1794-ib16d diagnostic input module compatibility – Rockwell Automation 1794-OB16D FLEX I/O Diagnostic Modules User Manual User Manual
Page 16
Publication 1794-UM061A-EN-P - July 2006
14 1794 FLEX I/O Diagnostic Digital Modules Overview
Network Compatibility
You can use the diagnostic modules with ControlNet, DeviceNet,
EtherNet/IP, or remote I/O networks.
1794-IB16D Diagnostic Input Module Compatibility
The 1794-IB16D diagnostic input module interfaces to sensing devices and
detects whether they are on or off. The diagnostic input module converts dc
signals from user devices to the appropriate logic level for use in the
FLEX I/O system. Typical input devices include these types of switches.
• Proximity switches
• Limit switches
• Photoelectric switches
• Selector switches
• Float switches
• Pushbutton switches
When designing a system using a FLEX I/O diagnostic input module, you
must consider:
• the voltage necessary for your application.
• current leakage through the input devices.
• the amount of current consumed by the input devices.
• whether the application requires sinking or sourcing devices.
Usage Limitations
Network
1794-IB16D
1794-OB16D
Remote I/O
Compatible with 1794-ASB
series E (or higher) and
1794-ASB2 series D (or higher)
remote I/O adapters.
Compatible with 1794-ASB
series D (or higher) and
1794-ASB2 series C (or higher)
remote I/O adapters.
DeviceNet
No limitations or constraints.
ControlNet
Direct connection only.
Direct or rack connections.
EtherNet/IP
Direct connection only.
Direct or rack connections.