Wiring output loads – Rockwell Automation 1794-OB16D FLEX I/O Diagnostic Modules User Manual User Manual
Page 30

Publication 1794-UM061A-EN-P - July 2006
28 About the FLEX I/O Diagnostic Output Module
Wiring Output Loads
You can use the 1794-OB16D diagnostic module with the 1794-TB2,
1794-TB3, or 1794-TB3S terminal base units.
User power can be wired to the (+) voltage and common terminals directly, or
power can be daisychained from the FLEX I/O terminal base units on the
DIN rail. Output channels are not isolated from one another. All 16 channels
share a common return (group isolation from FLEX I/O system-side logic
voltages).
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
34
Output Channel 0-15
Common
(1794-TB3 shown)
-V
Voltage
In +V
Voltage
Out +V
Voltage (24V dc)
Terminals 35 thru 50 not available on 1794-TB2
A
B
C
Common
-V
Common
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
FLEX TB2/3/3S
Terminal Base
A0-A15
B17-B32
C34
B16
Output
Common
V+
V-
Output
Device
24V dc
External User
Power Supply