Configure the qdc module's i/o chapter 3 – Rockwell Automation 1771-QDC, D17716.5.85(Passport) MNL. PLASTIC MOLDING MODULE User Manual
Page 47
Enter Your Alarm and TimeĆdelay Values Here
Configure the QDC Module's I/O
Chapter 3
3-16
Set Up Maximum RPM and Pressure Alarms, and Time Delays
The QDC module continuously monitors screw RPM, ram (screw)
pressure, and cavity pressure inputs. When it detects that the process input
equals or exceeds a preset alarm setpoint, the QDC module sets an alarm
bit. A setpoint of zero disables the associated alarm.
To guard against nuisance alarms caused by noise spikes or pressure
transients , you can set a time delay so the QDC module must monitor
continuous excessive pressure or RPM for an amount of time before setting
the high alarm. A setpoint of zero disables this delay.
Configure the QDC module for pressure and RPM alarms as follows:
1.
Determine these values for ram (screw) and/ or cavity pressure
alarms:
pressure-alarm setpoint
time-delay setpoint
2.
Determine these values for screw RPM alarms:
RPM-alarm setpoint
time-delay setpoint
3.
Record non-zero setpoints on Worksheet 3-G for the pressure alarms,
RPM alarm, and time delays you want to use.
4.
Download them to the QDC module using the procedures presented
earlier in this chapter:
Worksheet 3ĆG
Alarm and TimeĆdelay Setpoints
Control Word
ProĆSet 600 Addr.
Value
Description
Units
MCC21
N40:17
Screw PressureĆalarm Setpoint
Ram (screw) Pressure
2
MCC22
N40:18
ScrewĆpressure TimeĆdelay Setpoint
Time Measured in Seconds
1
MCC55
N40:51
HighĆRPM Alarm Setpoint
Rotational Speed
3
MCC56
N40:52
Screw RPM TimeĆdelay Setpoint
Time Measured in Seconds
1
MCC61
N40:57
Cavity PressureĆalarm Setpoint
Cavity Pressure
4
MCC62
N40:58
CavityĆpressure TimeĆdelay Setpoint
Time Measured in Seconds
1
1
Time Measured in Seconds
2
Pressure
3
Rotational Speed
4
Pressure
00.00 to 00.99
0000 to 9999 PSI
000.0 to 999.9 RPM
00000 to 20,000 PSI
000.0 to 999.9 Bar
0000.0 to 2000.0 Bar