Motor information, Motor data entry – Rockwell Automation 1560E SMC Flex Smart Motor Controller User Manual
Page 95
Programming
4-15
1560E-UM050B-EN-P - June 2013
Motor Information
The Basic Set Up and Overload programming group allows the user to set
parameters indicating to the controller which motor is connected. It is
important to correctly input the data to achieve the best performance from
your controller.
For overload protection, it is critical that the data be
entered as it appears on the motor nameplate.
Motor Data Entry
In the Program mode, enter the correct values into the Overload group:
Description
Option
Display
Overload Class vw
The factor default setting disables
overload protection. To enable it, enter
the desired trip class in this parameter.
Disable, 10, 15, 20,
30
Service Factor vw
Enter the value from the motor’s
nameplate.
0.01 to 1.99
Motor FLC uvw
Enter the value from the motor’s
nameplate.
1.0 to 1000A
Overload Reset vw
Allows the user to select either a manual
or auto reset after an overload.
Manual, Auto
Motor Connection w
Enter the type of motor being connected
to the SMC-Flex: Line or Delta
Line, Delta
Line Voltage uw
Enter the system voltage in this
parameter. This must be done to ensure
optimum motor performance and correct
operation of undervoltage and
overvoltage protection.
1 to 10,000 V
u
Refer to the SMC -Flex controller nameplate for maximum ratings. Exceeding these could result in
damage to the controller.
v
Found in Overload programming group. Only one location needs to be programmed.
w
Found in Basic Set Up programming group.