Rockwell Automation 1560E SMC Flex Smart Motor Controller User Manual
Page 171

Specifications
A-7
1560E-UM050B-EN-P - June 2013
Table A.7 – Power Fuses and Losses
Description
Specifications
Power Fuses and Fuse Holders
This section details the power fuse and fuse holder technical information that each medium voltage product
conforms to. It includes information on R-rated fuses, as well as mounting dimensions.
Fuse Types
R Rated :
2R to 24R
2R to 24R
19R, 38R
Interrupting Ratings : 2.4 kV to 7.2 kV
A480R – 5.0/2.4 kV
A072 – 7.2 kV
A051B – 5.0/2.4 kV
50 kA RMS SYM (80 kA RMS ASYM)
Mounting (Center) Dimensions
Clip-On
304.8 mm (12.0 in)
Bolt-On
454.2 mm (17.88 in)
Maximum Heat Dissipation (kW) (Convection)
Start or Stop Cycle
(@ 450% Starting Duty)
180 A 360 A 600 A
Continuous
2500 V
13.5
19.2
45.3
.250
5000 V
27.0
38.5
90.5
.250
Controller Rating
7200 V
40.5
57.7
136.0
.250
Power Losses
Current (A)
Fuse Size
Losses (kW)
± 10%
90
6R
.125
180
12R
.350
240
18R
.510
360
24R
1.000
Power Cell Losses
600
57X
1.500
Bus Rating (A)
Fully Loaded Bus
Losses per 915 mm (36 in.)
Section
(Watts) ±%
1200
150
2000
200
Power Bus Losses
3000
200
Control Power Transformer Losses
The losses from a 500 VA control power transformer fully
loaded are approximately 50 W per controller.
Low Voltage Panel Losses
The losses from the standard control circuit
are approximately 25 W per controller.