Table A.8 – Control Wire and Power Wire
Description
Specifications
Control Wire
All Medium Voltage structures shall be equipped with control wire which meets the following specifications:
Type
TEW, Stranded Copper Wire
(Tinned)
AWG Size (Control Circuit)
#14 AWG – 1.5 mm
2
AWG Size (Current Transformer Circuit)
#12 AWG – 2.5 mm
2
Number of Strands
19
Maximum Voltage Rating
600 V
Maximum Rated Temperature
105°C (221°F)
Terminal Blocks
1492-CA1, -CA3
Power Wire
Power wire used to feed the primary of the control power transformer or potential transformers is as follows :
AWG Size
#8 AWG
Type
Alcatel Excelene XLPE MV90
Insulation Rating Ê
5.0 kV
Maximum Temperature Rating
90°C (194°F)
The controller shall be wired with the following non-shielded, stranded wire type, based on the current ratings :
Controller
Rating (Amps)
AWG Size
Type
Insulation
Rating Ë
Maximum Temperature
Rating
200
#2
EP-CSPE MV90
8.0 kV
90°C (194°F)
400
#4/0
EP-CSPE MV90
8.0 kV
90°C (194°F)
600
(2) x #4/0
EP-CSPE MV90
8.0 kV
90°C (194°F)
Ê
For 7.2 kV rated controllers, #8 AWG — 8.0 kV EP-CSPE MV90, non-shielded stranded cable is used.
Ë
For 7.2 kV rated controllers, #2 AWG, #4/0 AWG, or 350 kcmil MCM – 8.0 kV EP-CSPE MV90, non-shielded
stranded cable is used.