Table 9.A – Fault Display Explanation (cont.)
Display
Fault Code
Possible Causes
Possible Solutions
Phase Reversal
26
• Incoming supply voltage is not in
the expected ABC sequence
• Check power wiring
• Disable protection if not needed
Comm Loss
27, 28, 29
• Communication disconnection at
the serial port
• Check for a communication cable disconnection to the
SMC-Flex controller
Network
30, 31, 32
• DPI network loss
• Reconnect for each DPI connected device
Ground Fault
33
• Ground fault current level has
exceeded programmed values
• Check power system and motor; correct if necessary
• Check programmed ground fault levels to match
application requirements
Excess Starts/Hr.
34
• Number of starts in a one-hour
period has exceeded the value
programmed
• Wait an appropriate amount of time to restart
• Consult factory if more than 2 starts per hour are
required
Power Loss
:
(with phase indication)
35, 36, 37
• Missing supply phase (as indicated)
• Loss of feedback
• Check for open line (i.e., blown line fuse)
• Check CT connections, replace Interface board
Hall ID
38
• Faulty interface
• Check ribbon cable connections between interface
board and control module
• Replace interface board
NVS Error
39
• Data entry error
• Check user data and perform a User Store function
• Replace control module
System Faults
128 to 209
• Control module internal fault
• Cycle control power to reset the control module
• If fault persists, replace control module
: Prestart fault indication
Table 9.B – Motor Will Not Start – No Output Voltage to the Motor
Display
Possible Causes
Possible Solutions
Fault displayed
• See fault description
• See Table 9.A addressing fault conditions
Display is blank
• Control voltage is absent
• Failed control module
• Check control wiring and correct if necessary
• Replace control module
Stopped
0.0 Amps
• Pilot devices
• SMC Enable input is open at
terminal 13
• Terminal 16 is open
• Start-Stop control has not been
enabled for the human interface
module
• Control voltage
• Failed control module
• Check wiring
• Check wiring
• Check wiring
• Follow the instructions on page 2-16 to 2-18
to enable control capability
• Check control voltage
• Replace control module
Starting
• Two or three power phases are
missing
• Check power system
• Check voltage sensing module and connections
Table 9.C – Motor Rotates (but does not accelerate to full speed)
Display
Possible Causes
Possible Solutions
Fault displayed
• See fault description
• See Table 9.A addressing fault conditions
Starting
• Mechanical problems
• Inadequate Current Limit setting
• Failed control module
• Check for binding or external loading and correct
• Check motor
• Adjust the Current Limit Level to a higher setting
• Replace control module