beautypg.com

Fault codes, Fault contact – Rockwell Automation 1560E SMC Flex Smart Motor Controller User Manual

Page 107

background image

Diagnostics

7-3

1560E-UM050B-EN-P - June 2013

Fault Codes

Table 7.A provides a complete cross-reference of the available fault codes
and corresponding fault descriptions.

Table 7.A
Fault Code Cross-Reference

Fault

Code

Fault

Code

Line Loss A

1

Underload

23

Line Loss B

2

Jam

24

Line Loss C

3

Stall

25

Shorted SCR A

4

Phase Reversal

26

Shorted SCR B

5

Coms Loss P2

27

Shorted SCR C

6

Coms Loss P3

28

Open Gate A

7

Coms Loss P5

29

Open Gate B

8

Network P2

30

Open Gate C

9

Network P3

31

PTC Pwr Pole

10

Network P5

32

SCR Overtemp Ê

11

Ground Fault

33

Motor PTC

12

Excess Starts/Hour

34

Open Bypass A

13

Power Loss A

35

Open Bypass B

14

Power Loss B

36

Open Bypass C

15

Power Loss C

37

No Load A

16

Hall ID

38

No Load B

17

NVS Error

39

No Load C

18

No Load

40

Line Imbalance

19

Line Loss A

41

Overvoltage

20

Line Loss B

42

Undervoltage

21

Line Loss C

43

Overload

22

Ê

Not applicable in MV applications.

Fault Contact

The auxiliary contact is located at terminals 29 and 30. Note that the state
this contact takes upon power-up (normally open or normally closed) can be
programmed. These parameters can be found in either Basic Setup or the
Linear List groups when modifying parameters in the Set Up mode.