Parameter modification – Rockwell Automation 1560E SMC Flex Smart Motor Controller User Manual
Page 88
4-8
Programming
1560E-UM050B-EN-P - June 2013
Parameter Modification
All parameters are modified using the same method. The basic steps to
performing parameter modification are described below.
Note:
Parameter values modified while the motor is operating are not
valid until the next start sequence begins.
Description
Action
Display v
–
–
1. Press the ESC key to go from the
status display to the Main menu.
Esc
Esc
—
2. Scroll with the Up/Down keys until
the Preferences option is
highlighted.
3. Press the Enter key to access the
Parameter menu.
4. Scroll with the Up/Down keys
until the option you want to use
(Monitoring, Motor Protection,
etc.) is highlighted. For this
example, Set Up will be used.
5. Press Enter to select the Set Up
group.
—
6. Scroll to Basic Set Up and press
Enter. u
7. Scroll to the Starting Mode
parameter by using the Up/Down
keys, and press Enter.
8. Press Enter to select the option.
Scroll to the option of your choice
by using the Up/Down keys. For
this example, we will choose
Current Limit.
9. Press the Enter key to accept the
new setting.
—
10. Scroll to the next parameter by
using the Down key. Continue
the process until all desired
settings are entered.
11. To save modifications to memory,
scroll to Parameter Mgmt, press
Enter twice and scroll to User
Store. Press the Enter key again
to save the new settings to
EEPROM.
u
The SMC Option advises the user if any control option (i.e., Pump Control) is resident. This parameter is
factory set and cannot be modified by the user.
v
The display will indicate that the second line is now active by highlighting the first character. If the LCD
display does not provide a highlighted cursor, then the controller is in the Display mode.