Parameter Descriptions

• Wiring mode – selected to match the physical connections to the power

system
– Direct Delta
– Open Delta
– Wye
– Single phase
– 1 PT 1 CT - LL
– 1 PT 1 CT - LN

PT (VT) primary voltage – reflects the voltage rating on the high side of

the potential/voltage transformers. Range 1…50,000V, default 480V

PT (VT) secondary voltage – reflects the voltage rating on the low side of

the potential/voltage transformers. Range 1…600 V, default 480V

CT primary current – reflects the current rating on the high side of the

phase current transformers. Range 1…50,000 A, default 5. The CT
secondary current is also adjustable but the default value of 5 A is standard

IP address, subnet mask, default gateway – Ethernet port settings

required for communications with the user’s local area network

Set Parameters with the PowerMonitor 1000 Unit

The Basic Configuration table contains the configuration parameters needed for
initial setup of the PowerMonitor meter in the base system.

The diagram and table shows the LCD interface buttons and their functions.

Figure 4 - LCD Interface

The buttons function differently in each mode. The PowerMonitor 1000 unit
enters into Display mode by default.