Parameter descriptions, Set parameters with the powermonitor 1000 unit – Rockwell Automation 1413-CAP-ME-PE Capacitor Bank Controller, Series C User Manual
Page 43
Rockwell Automation Publication 1413-UM001D-EN-P - November 2010
43
Configuration Chapter 3
Parameter Descriptions
• Wiring mode – selected to match the physical connections to the power
system
– Direct Delta
– Open Delta
– Wye
– Single phase
– 1 PT 1 CT - LL
– 1 PT 1 CT - LN
• PT (VT) primary voltage – reflects the voltage rating on the high side of
the potential/voltage transformers. Range 1…50,000V, default 480V
• PT (VT) secondary voltage – reflects the voltage rating on the low side of
the potential/voltage transformers. Range 1…600 V, default 480V
• CT primary current – reflects the current rating on the high side of the
phase current transformers. Range 1…50,000 A, default 5. The CT
secondary current is also adjustable but the default value of 5 A is standard
• IP address, subnet mask, default gateway – Ethernet port settings
required for communications with the user’s local area network
Set Parameters with the PowerMonitor 1000 Unit
The Basic Configuration table contains the configuration parameters needed for
initial setup of the PowerMonitor meter in the base system.
The diagram and table shows the LCD interface buttons and their functions.
Figure 4 - LCD Interface
The buttons function differently in each mode. The PowerMonitor 1000 unit
enters into Display mode by default.
Powermonitor 1000
RS-485
STATUS
RX TX Mod Net
Up Arrow
Escape
Enter
Down Arrow