Rockwell Automation 1413-CAP-ME-PE Capacitor Bank Controller, Series C User Manual
Page 35

Rockwell Automation Publication 1413-UM001D-EN-P - November 2010
35
Configuration Chapter 3
N7:10
Capacitor Step 1 -
Effective Size
kVAR
Nameplate capacitor size for each step
Yes
50
Configuration
N7:11
Capacitor Step 2 -
Effective Size
kVAR
Yes
(2)
50
Configuration
N7:12
Capacitor Step 3 -
Effective Size
kVAR
Yes
50
Configuration
N7:13
Capacitor Step 4 -
Effective Size
kVAR
Yes
50
Configuration
N7:14
Capacitor Step 5 -
Effective Size
kVAR
Yes
50
Configuration
N7:15
Capacitor Step 6 -
Effective Size
kVAR
Yes
50
Configuration
N7:16
Capacitor Step 7 -
Effective Size
kVAR
Yes
50
Configuration
N7:17
Capacitor Step 8 -
Effective Size
kVAR
Yes
50
Configuration
N7:18
Capacitor Step 9 -
Effective Size
kVAR
Yes
50
Configuration
N7:19
Capacitor Step 10 -
Effective Size
kVAR
Yes
50
Configuration
N7:30
Capacitor
Discharge Time
seconds
The amount of time after a capacitor step is
turned off, before a capacitor step is
considered fully discharged
Yes
60
Configuration
N7:31
Nominal Voltage
volts
The nominal bus voltage of the system
Yes
480
Ext Configuration 1
N7:32
Voltage Threshold
- High and Low
%
The voltage percentage from nominal, that
will determine high and low limits for
alarming
Yes
1…10
5
Ext Configuration 1
N7:34
Lead Deadband
kVAR
The leading kVAR limit allowed for the
system, before the controller acts to correct
lead, typically 33% of smallest capacitor step
Yes
20
Configuration
N7:35
Lag Deadband
kVAR
The lagging kVAR limit allowed for the
system, before the controller acts to correct
lag, typically 66% of largest capacitor step
Yes
35
Configuration
N7:36
Step Tolerance
Low Limit
%
The kVAR percentage of effective, that will
determine low limits for each capacitor step
Yes
0…10
5
Ext Configuration 2
N7:37
Power Factor Out-
of-Range Time
seconds
The amount of time the system kVAR must be
out of the range of the lead or lag deadband,
before the controller acts to correct
Yes
60
Ext Configuration 1
N7:39
Step Tolerance
Time
seconds
The amount of time after a capacitor step is
actuated, before taking a sample reading of
the system kVAR difference, to determine if
the capacitor step is above the step tolerance
low limit
Yes
30
Ext Configuration 2
N7:40
Voltage High In-
Range Time
seconds
The amount of time the bus voltage must be
below the high limit before resetting the
Voltage High Alarm
Yes
120
Ext Configuration 1
N7:41
Voltage Low In-
Range Time
seconds
The amount of time the bus voltage must be
above the low limit before resetting the
Voltage Low Alarm
Yes
120
Ext Configuration 1
Table 9 - Control and Status Parameters
Address
Parameter
Unit
Description
Configurable Range
Default
PanelView
Component
Screen