Minimum spacing, Mounting angle, Panel guidelines – Rockwell Automation 1413-CAP-ME-PE Capacitor Bank Controller, Series C User Manual
Page 19: Panel cutout dimensions
Rockwell Automation Publication 1413-UM001D-EN-P - November 2010
19
Installation Chapter 2
Minimum Spacing
Plan for adequate space around the terminal, inside the enclosure, for ventilation
and cabling. Consider heat produced by other devices in the enclosure. The
ambient temperature around the terminal must be 0…50 °C (32…122 °F).
Mounting Angle
You can mount the terminal vertically against the panel, or tilted forward or
backwards, up to a 45° angle. For mounting angles greater than 45°, the operating
temperature is restricted to 40 °C (104 °F).
Panel Guidelines
Supporting panels must be at least 16 gauge to provide proper sealing against
water and dust and to provide proper support. The panel surface must be flat and
free of imperfections to maintain an adequate seal and NEMA Type ratings.
Panel Cutout Dimensions
Use the template shipped with your terminal to mark the cutout dimensions.
PanelView
Component
Top
Bottom
Sides
Back
C200 and C300 Keypad
C600 Touch
51 mm (2 in.)
51 mm (2 in.)
25 mm (1 in.)
13 mm (0.5 in.)
TIP
The minimum spacing requirements are sufficient for connecting cables
and inserting or removing a memory card. Plan for additional clearance if
using the USB host port on the back of the unit.
PanelView Component Terminal
Height, Approx., mm (in.) Width, Approx., mm (in.)
C600 Touch
135.0 ± 1.0 (5.31 ± 0.04)
189.0 ± 1.0 (7.44 ±0.04)