Chapter 3 Configuration

N7:42

Voltage In-Range
Time

seconds

The amount of time after the Voltage High
and Voltage Low alarms have been reset,
before signifying that the voltage is in an
acceptable range

Yes

120

Ext Configuration 1

N7:43

Control Word

(1)

This is the control word for the capacitor
bank controller. Bit 4 is used to initiate a
restore of factory defaults. This should be
treated as a momentary state. Bit 5 is used to
initiate the step size buffer. This bit should
also be treated as a momentary state. Bit 6 is
used for disabling step tolerance. The BCD
value for each bit is available for easy setup

Yes
See

Table 10

,

Control Word
(N7:43)

for

more
information.

Ext Configuration 2

N7:45

Number of
PowerMonitor
1000 meters

The number of PowerMonitor meters to
include in the aggregate kW and kVAR
calculations

Yes

1…4

1

Configuration

N7:46

Number of
Capacitor Steps

The number of capacitor steps to be
controlled

Yes

1…10

10

Configuration

N7:47

Operating Mode

The operating mode:
0 - Manual
1 - FILO
2 - Balanced
3 - Best Fit

Yes

0…3

0

Configuration

N7:56

Nominal Voltage
Scale

Multiplier scale 1, 10, 100, or 1000

Yes

1

Ext Configuration 1

N7:59

Number of
Samples

The number of kVAR samples to average
together when auto-configuring capacitor
step sizes

Yes

1…10

5

Ext Configuration 1

N139:10

Write IP address

Writes IP address for the PowerMonitor 1000
meter to MicroLogix 1400 controller for
messaging (Bit 0), toggle bit 0 to 1 to 0

Yes

Admin

N139:12

PowerMonitor 1 IP
Byte A

1st byte (octet) of PowerMonitor IP Address

Yes

0…255

192

Admin

N139:13

PowerMonitor 1 IP
Byte B

2nd byte (octet) of PowerMonitor IP Address

Yes

0…255

168

Admin

N139:15

PowerMonitor 1 IP
Byte C

3rd byte (octet) of PowerMonitor IP Address

Yes

0…255

254

Admin

N139:16

PowerMonitor 1 IP
Byte D

4th byte (octet) of PowerMonitor IP Address

Yes

0…255

64

Admin

N139:22

PowerMonitor 2 IP
Byte A

1st byte (octet) of PowerMonitor IP Address

Yes

(3)

0…255

192

Admin

N139:23

PowerMonitor 2 IP
Byte B

2nd byte (octet) of PowerMonitor IP Address

Yes

(3)

0…255

168

Admin

N139:25

PowerMonitor 2 IP
Byte C

3rd byte (octet) of PowerMonitor IP Address

Yes

(3)

0…255

254

Admin

N139:26

PowerMonitor 2 IP
Byte D

4th byte (octet) of PowerMonitor IP Address

Yes

(3)

0…255

65

Admin

N139:32

PowerMonitor 3 IP
Byte A

1st byte (octet) of PowerMonitor IP Address

Yes

(3)

0…255

192

Admin

N139:33

PowerMonitor 3 IP
Byte B

2nd byte (octet) of PowerMonitor IP Address

Yes

(3)

0…255

168

Admin

Table 9 - Control and Status Parameters

Address

Parameter

Unit

Description

Configurable Range

Default

PanelView
Component
Screen