Rockwell Automation 1413-CAP-ME-PE Capacitor Bank Controller, Series C User Manual
Page 36
36
Rockwell Automation Publication 1413-UM001D-EN-P - November 2010
Chapter 3 Configuration
N7:42
Voltage In-Range
Time
seconds
The amount of time after the Voltage High
and Voltage Low alarms have been reset,
before signifying that the voltage is in an
acceptable range
Yes
120
Ext Configuration 1
N7:43
Control Word
(1)
This is the control word for the capacitor
bank controller. Bit 4 is used to initiate a
restore of factory defaults. This should be
treated as a momentary state. Bit 5 is used to
initiate the step size buffer. This bit should
also be treated as a momentary state. Bit 6 is
used for disabling step tolerance. The BCD
value for each bit is available for easy setup
Yes
See
Table 10
,
Control Word
(N7:43)
for
more
information.
Ext Configuration 2
N7:45
Number of
PowerMonitor
1000 meters
The number of PowerMonitor meters to
include in the aggregate kW and kVAR
calculations
Yes
1…4
1
Configuration
N7:46
Number of
Capacitor Steps
The number of capacitor steps to be
controlled
Yes
1…10
10
Configuration
N7:47
Operating Mode
The operating mode:
0 - Manual
1 - FILO
2 - Balanced
3 - Best Fit
Yes
0…3
0
Configuration
N7:56
Nominal Voltage
Scale
Multiplier scale 1, 10, 100, or 1000
Yes
1
Ext Configuration 1
N7:59
Number of
Samples
The number of kVAR samples to average
together when auto-configuring capacitor
step sizes
Yes
1…10
5
Ext Configuration 1
N139:10
Write IP address
Writes IP address for the PowerMonitor 1000
meter to MicroLogix 1400 controller for
messaging (Bit 0), toggle bit 0 to 1 to 0
Yes
Admin
N139:12
PowerMonitor 1 IP
Byte A
1st byte (octet) of PowerMonitor IP Address
Yes
0…255
192
Admin
N139:13
PowerMonitor 1 IP
Byte B
2nd byte (octet) of PowerMonitor IP Address
Yes
0…255
168
Admin
N139:15
PowerMonitor 1 IP
Byte C
3rd byte (octet) of PowerMonitor IP Address
Yes
0…255
254
Admin
N139:16
PowerMonitor 1 IP
Byte D
4th byte (octet) of PowerMonitor IP Address
Yes
0…255
64
Admin
N139:22
PowerMonitor 2 IP
Byte A
1st byte (octet) of PowerMonitor IP Address
Yes
(3)
0…255
192
Admin
N139:23
PowerMonitor 2 IP
Byte B
2nd byte (octet) of PowerMonitor IP Address
Yes
0…255
168
Admin
N139:25
PowerMonitor 2 IP
Byte C
3rd byte (octet) of PowerMonitor IP Address
Yes
0…255
254
Admin
N139:26
PowerMonitor 2 IP
Byte D
4th byte (octet) of PowerMonitor IP Address
Yes
0…255
65
Admin
N139:32
PowerMonitor 3 IP
Byte A
1st byte (octet) of PowerMonitor IP Address
Yes
0…255
192
Admin
N139:33
PowerMonitor 3 IP
Byte B
2nd byte (octet) of PowerMonitor IP Address
Yes
0…255
168
Admin
Table 9 - Control and Status Parameters
Address
Parameter
Unit
Description
Configurable Range
Default
PanelView
Component
Screen