beautypg.com

Using the battery – Rockwell Automation 1413-CAP-ME-PE Capacitor Bank Controller, Series C User Manual

Page 15

background image

Rockwell Automation Publication 1413-UM001D-EN-P - November 2010

15

Installation Chapter 2

4.

Unhook the top of the DIN rail slot from the rail.

Panel Mounting

Mount to panel by using #8 screws. Follow these steps to install your controller
with mounting screws.

1.

Remove the mounting template from inside the back cover of this
document.

2.

Secure the template to the mounting surface, making sure your controller is
spaced properly (see

Controller Spacing on page 13

for more

information).

3.

Drill holes through the template.

4.

Remove the mounting
template.

5.

Mount the controller.

6.

Leave the protective debris
strip in place until you are
finished wiring the controller
and any other devices

Using the Battery

The MicroLogix 1400 controller is equipped with a replaceable battery (catalog
number 1747-BA). The Battery Low indicator on the LCD display of the
controller shows the status of the replaceable battery. When the battery is low, the
indicator is set (displayed as a solid rectangle). This means that either the battery
wire connector is disconnected, or the battery may fail within 2 days if it is
connected.

This product contains a sealed lithium battery which may need to be
replaced during the life of the product.

At the end of its life, the battery contained in this product should be collected
separately from any unsorted municipal waste.

The collection and recycling of batteries helps protect the environment and
contributes to the conservation of natural resources as valuable materials
are recovered.

ESC

OK

Open

Closed

ESC

OK

Mounting Template

This manual is related to the following products: