Access to the power bus, Rear access, Refer to – Rockwell Automation 1512B MV Controllers, 200/400A Two-High Cabinet, Standard and Arc-Resistant Enclosure User Manual
Page 17
Rockwell Automation Publication 1500-UM055G-EN-P - May 2013
9
Installation – Standard Enclosure
Chapter 2
5. Secure the sections together using the 1/4-20 self-tapping screws. Thread
the screw through the 7 mm (0.281 in.) clearance hole to the
corresponding 6 mm (0.219 in.) pilot hole. To access the front clearance
holes of the left-side cabinet, open the medium voltage doors. To access the
rear clearance holes remove the rear covers of the starter. If rear access is
not available, refer to
Front Access– Access to Power Bus on page 11
.
6. Secure the right section to the floor using 12 mm (1/2 in. [M12]) floor
mounting bolts (refer to
Figure 6 - Joining Sections
Access to the Power Bus
Rear Access
1. Remove the hardware securing the center rear bus access cover (see
2. Remove the center rear bus access cover.
Fron
t
Fro
nt
Side Bus
Access Cover
0.219 Pilot
Holes (5x)
0.281 Pilot
Holes (5x)
0.281 Pilot
Holes (5x)
0.219 Pilot
Holes (3x)
ATTENTION: This procedure requires contact with medium voltage
components. To avoid shock hazards, lock out incoming power before working
on the equipment (refer to
Power Lock-out Procedure on page 47 of Chapter 5
Verify with a hot stick or appropriate voltage measuring device that all circuits
are voltage free. Failure to do so may result in severe burns, injury or death.