General Information
Chapter 1
Prepared Space
When ordering a starter kit to complete a prepared space
(2)
, provide the
following information to ensure the proper components are supplied.
Series Number
Provide the series number from the structure with the prepared space. The
number is stamped on a nameplate on the right-hand flange of the starter (see
). The series number is also available from the dimension drawings for
the starter.
Motor Data
Provide the following motor data:
• Locked rotor current
• Full load current
• Maximum locked rotor time
• Acceleration time
• Motor service factor
• Motor horsepower
Starter Features
Provide information regarding any special features required for the starter kit.
Indicate if these features are different from the motor control features in the
existing, complete power cell.
Recommended Torque
Values
When reinstalling components or when reassembling the cabinet, tighten the
following bolt sizes to the specified torque values:
Table 1 - Hardware Torque Values
(2) Not available on arc resistant cabinets.
1/4 in. hardware
8 N•m (6 lb•ft)
5/16 in. hardware
15 N•m (12 lb•ft)
3/8 in. hardware
27 N•m (20 lb•ft)
1/2 in. hardware
65 N•m (48 lb•ft)