B-4
WIM Parameters
05
[Reset Module]
No action if set to “Ready.” Resets the WIM if set to
“Reset Module.” Restores the WIM to its factory default
settings if set to “Set Defaults.” This parameter is a
command. It will be set to “0 = Ready” after the
command has been performed.
Default:
0 = Ready
Values:
0 = Ready
1 = Reset Module
2 = Set Defaults
Type:
Read/Write
Reset Required: No
06
[Clear DF1 Counts]
No action if set to “Ready.” Resets the DF1 statistical
parameters 10 and 11 to 0 if set to “1 = Clear Counts.”
This parameter is a command. It will be reset to
“0 = Ready” after a “Clear Counts” command has been
performed.
Default:
0 = Ready
Values:
0 = Ready
1 = Clear Counts
Type:
Read/Write
Reset Required: No
07
[DF1 Packets Sent]
Displays the number of DF1 packets sent by the WIM.
The value of this parameter is normally approximately
equal to the Parameter 11 - [DFI Packets Rcvd] value.
Default:
0
Minimum:
0
Maximum:
4294967295
Type:
Read Only
08
[DF1 Packets Rcvd]
Displays the number of DF1 packets received by the
WIM. The value of this parameter is normally
approximately equal to the Parameter 10 - [DFI
Packets Sent] value.
Default:
0
Minimum:
0
Maximum:
4294967295
Type:
Read Only
No.
Name and Description
Details
!
ATTENTION: Risk of injury or equipment damage exists.The drive will fault
when you remove or reset the WIM. Determine how the drive will respond before
removing or resetting the WIM.