WIM Parameters

Parameter List for DPI Products

No.

Name and Description

Details

01

[DPI Port]
Displays the port on the drive to which the WIM is
connected.

Default:

0

Minimum:

0

Maximum:

7

Type:

Read Only

02

[Comm Flt Action]
Sets the action that the WIM and drive will take if the
WIM detects that wireless communications are
disrupted. This setting is effective only if control I/O is
transmitted through the WIM.

Default:

0 = Fault

Values:

0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last

Type:

Read/Write

Reset Required: No

03

[Security Mode]
Enables/disables the security mode for the WIM, which
prevents accessing its parameters and the connected
drive for configuration.

Default:

0

Values:

0 = PIN Not Req’d
1 = PIN Required

Type:

Read/Write

Reset Required: Yes

04

[Security PIN]
Sets the PIN number to access WIM parameters for
configuration when Parameter 03 - [Security Mode] is
set to 1 = PIN Required. See

Page 3-25

for details.

Default:

0

Minimum:

0

Maximum:

9999

Type:

Read/Write

Reset Required: Yes

05

[Reset Module]
No action if set to “Ready.” Resets the WIM if set to
“Reset Module.” Restores the WIM to its factory default
settings if set to “Set Defaults.” This parameter is a
command. It will be set to “0 = Ready” after the
command has been performed.

Default:

0 = Ready

Values:

0 = Ready
1 = Reset Module
2 = Set Defaults

Type:

Read/Write

Reset Required: No

06

[Ref/Fdbk Size]
Displays the size of the Reference/Feedback. The drive
determines the size of the Reference/Feedback. The
WIM automatically uses the correct size.

Default:

0 = 16-bit

Value:

0 = 16-bit
1 = 32-bit

Type:

Read Only

07

[Datalink Size]
Displays the size of each Datalink word. The drive
determines the size of Datalinks.

Default:

0 = 16-bit

Values:

0 = 16-bit
1 = 32-bit

Type:

Read Only

08

[DPI Data Rate]
Displays the data rate used by the DPI drive. This data
rate is set in the drive, and the WIM autobauds to it.

Default:

0

Values:

0 = 125 kbps
1 = 500 kbps

Type:

Read Only

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 02 -
[Comm Flt Action]
lets you determine the action of the WIM and connected
drive if communications are disrupted. By default, this parameter faults the drive.
You can set this parameter so that the drive continues to run. Precautions
should be taken to ensure that the setting of this parameter does not create a
risk of injury or equipment damage. When commissioning the drive, verify that
your system responds correctly to various situations (for example, loss of
wireless communication).

!

ATTENTION: Risk of injury or equipment damage exists.The drive will fault
when you remove or reset the WIM. Determine how the drive will respond before
removing or resetting the WIM.