Viewing and clearing events, To view the event queue, Events – Rockwell Automation 7000 DPI Wireless Interface Module User Manual
Page 52: Viewing and clearing events -4

4-4
Troubleshooting
The WIM maintains an event queue that reports the history of its actions.
You can view the event queue with the following tools:
• For Pocket PCs, use Pocket DriveExplorer for Pocket PC software
(version 1.01 or higher).
• For laptop or desktop computers, use DriveExplorer software
(version 4.04 or higher), DriveExecutive software (version 3.01 or
higher).
• An LCD PowerFlex 7-Class HIM.
To view the event queue
1. Access the event queue using a configuration tool.
2. Scroll through events in the event queue.
Events
Many events in the Event queue occur under normal operation. If you
encounter unexpected communications problems, the events may help
you or Allen-Bradley personnel troubleshoot the problem. The following
events may appear in the event queue:
DPI Product Event List
Viewing and Clearing Events
Event
Description
Control Disabled
The WIM has sent a “Soft Control Disable” command to the DPI drive.
Control Enabled
The WIM has sent a “Soft Control Enable” command to the DPI drive.
DPI Bus Off Flt
A bus-off condition was detected on DPI. This event may be caused by loose or
broken cables or by noise.
DPI Fault Clear
The DPI drive has issued a fault clear message.
DPI Fault Msg
The drive entered a faulted state.
Dup. Port Flt
Another peripheral with the same port number is already in use.
EEPROM Sum Flt The EEPROM in the WIM is corrupt.
Host Sent Reset
The DPI drive issued this event because it was reset.
Message Timeout
The DPI drive did not respond to a message request. Verify the cables are
correct.
No Event
Empty event queue entry.
Normal Startup
WIM initially powered up or was reset.
Online @ 125kbps The WIM and DPI drive are communicating at 125kbps.
Online @ 500kbps The WIM and DPI drive are communicating at 500kbps.