Diagnostics
The following codes can be used for diagnostics purposes:
Code
Information displayed
Information
C2459
CAN−AUX operating status
Chapter 6.11.1
^ 6−11
C2460
Number of the telegrams sent and received
Chapter 6.11.2
^ 6−12
C2461
Bus load (in %)
Chapter 6.11.3
^ 6−13
·
Settings cannot be carried out via these codes.
6.11.1
Operating status of the CAN−AUX interface
Via C2459 you can have the operating status of the system bus displayed:
Code
LCD
Possible settings
Information
Lenze
Selection
C2459 CAN1 state
g
0
Operational
1
Pre−operational
2
Warning
3
Bus off
System bus status (CAN−AUX)
C2459
Operating status
Information
0
Operational
The system bus is fully functional. The PLC can transmit and receive parameter and process data.
1
Pre−operational
The PLC can transmit and receive parameter data. Process data, however, are ignored.
A status change from Pre−operational to Operational can be effected by:
·
the CAN master
^ 3−2
·
a reset node
– via C2458, if the PLC has been configured as a "quasi" master.
^ 6−8
– via the binary input signal "Reset node" at the CANaux_Management SB
^ 7−20
2
Warning
The PLC has received faulty telegrams and is only involved in the system bus passively, i. e. no data can be
sent from the PLC anymore.
Possible causes:
·
Missing bus termination
·
Non−sufficient shielding
·
Differences in potential with regard to the earth connection of the control electronics
·
Bus load too high
·
PLC is not connected to the system bus.
3
Bus−off
The PLC has disconnected from the system bus due to too many faultily received telegrams.
·
The response to this status can be configured via C2484.
^ 6−9