Identifiers of the process data objects
The identifiers for the FIF_CAN1_IO ... FIF_CAN3_IO process data objects are generated by the
so−called basic identifier and the node address set in C2450:
Identifier + basic identifier ) node address
Basic identifier
dec
hex
PDOs
FIF_CAN1_IO (cyclic process data)
FIF−CAN1_IN
512
200
FIF−CAN1_OUT
384
180
FIF_CAN2_IO (event− or time−controlled process data)
FIF−CAN2_IN
640
280
FIF−CAN2_OUT
641
281
FIF_CAN3_IO (event− or time−controlled process data)
FIF−CAN3_IN
768
300
FIF−CAN3_OUT
769
301
5.4.1
Allocation of individual identifiers
For greater system bus networks with many nodes it can be reasonable to set individual identifiers
for the process data objects FIF_CAN1_IO ... FIF_CAN3_IO via C2453/C2454, which are
independent of the node address set in C2350:
1. Set C2453/x to "1".
– (x = subcode of the corresponding process data object):
Code
LCD
Possible settings
Information
Lenze
Selection
C2453 CAN addr sel
0
Identifier assignment under C2450 + basic
identifier
1
Identifier assignment under C2454/x
Source for the identifiers of the
process data objects
·
Save changes with C0003 = 1.
·
Changes are only valid after
reset node!
1 CAN addr sel1
0
FIF−CAN1_IN/OUT
2 CAN addr sel2
0
FIF−CAN2_IN/OUT
3 CAN addr sel3
0
FIF−CAN3_IN/OUT
2. Set the value which, added to "384", makes the desired identifier in C2453/x.
– (x = subcode of the corresponding process data object):
Code
LCD
Possible settings
Information
Lenze
Selection
C2454 CAN addr
1
{1}
512 Specification of individual
identifiers of the process data
objects
1
2
3
4
5
6
IN1 addr2
OUT1 addr2
IN2 addr2
OUT2 addr2
IN3 addr2
OUT3 addr2
129
1
257
258
385
386
FIF−CAN1_IN
FIF−CAN1_OUT
FIF−CAN2_IN
FIF−CAN2_OUT
FIF−CAN3_IN
FIF−CAN3_OUT