7 synchronisation, 1 canaux sync response, 2 canaux sync identifiers – Lenze DDS System bus CAN for PLC User Manual
Page 81: 3 canaux sync tx transmission cycle, Synchronisation, Canaux sync response, Canaux sync identifiers, Canaux sync tx transmission cycle, System bus (can) for lenze plc devices, Configuration (can−aux interface)

System bus (CAN) for Lenze PLC devices
Configuration (CAN−AUX interface)
6−7
l
PLC−Systembus EN 2.0
6.7
Synchronisation
Tip!
By means of the CAN_Synchronization SB, the internal time base of the PLC can be synchronised
with the arrival of the sync telegram.
Thus the internal calculating processes (e. g. control−oriented processes) of the PLC can be
synchronised with the calculating processes of other nodes which can also process the sync
telegram.
Detailed information on the CAN_Synchronization SB can be found in chapter 7.7.
(
^ 7−23)
6.7.1
CANaux sync response
The response to the reception of a sync telegram can be configured via C2466:
Code
LCD
Possible settings
IMPORTANT
Lenze
Selection
C2466 Sync response
1
CANaux sync response
0
No response
No response
1
Response to sync
PLC responds to a sync telegram
by sending the CANaux1_OUT
object.
6.7.2
CANaux sync identifiers
The transmission or reception identifiers of the sync telegram can be configured via C2467/C2468:
Code
LCD
Possible settings
IMPORTANT
Lenze
Selection
C2467 Sync Rx Id
128
1
{1}
256 CANaux sync Rx identifier
Receive identifier for the sync
telegram
C2468 Sync Tx Id
128
1
{1}
256 CANaux sync Tx identifier
Send identifier for the sync
telegram
6.7.3
CANaux sync Tx transmission cycle
The cycle time within which a sync telegram with the identifier set in C2468 is transmitted can be
configured via C2469:
Code
LCD
Possible settings
IMPORTANT
Lenze
Selection
C2469 Sync Tx time
0
0
{1 ms}
65000
0 = Off
CANaux sync time
Sync transmission telegram cycle