14

SmartPack Wall Mount Installation Manual

Connect ESD Ground

For installations with SmartLink data runs (Belden 8471) installed in grounded metal

conduit there is no need to run or terminate an additional ESD drain wire. For installations

not installed in grounded metal conduit follow the instructions below for ESD

termination.

Step 1:

Locate the grounding lug on the tray of the I/O panel, just to the right of the I/O

termination board.

Step 2:

Loosen, but do not remove, the set screw on the grounding lug.

Step 3:

Strip 6.35mm (1/4”) of insulation from the end of the 2.5mm

2

ESD drain wire(s)

and twist together.

Step 4:

Insert the bare end into the grounding lug and secure with the set screw.

DMX 512

Two 8 position receptacles are provided on the I/O termination board, one for DMX In and

the other for DMX-Thru. Prior to connecting DMX, follow the instructions for Belden 9729

cable preparation as defined on the single sheet instructions packaged with the 8 position

pluggable screw connector. A cable preparation kit for installation of CAT 5 cable (ETC part

number 4100A1013) is available for purchase, contact ETC for details.

Connect DMX

Step 1:

For DMX In and DMX Pass-Thru using Belden 9729 as recommended, prepare

the Belden cable as described in the DMX Cable Preparation kit instructions.

Step 2:

Using the 8 position pluggable screw connector provided in the cable preparation

kit, connect Shield (Com), DMX- and DMX+ as indicated in the graphic above.

Step 3:

DMX Pass-Thru using Belden 9729 can utilize the same pluggable screw

connector as DMX In. Connect Shield (Com), DMX - and DMX + as indicated in

the graphic above.

(J4) DMX IN

(J5) DMX
PASS-THRU

COM

DMX-

DMX+

DA

T

A

-

DA

T

A

+

6

7

8

ISOCOM

DMX-

DMX+

DA

T

A

-

DA

T

A

+

6

7

8

7021B5602

preliminary

1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

n/c

n/c

n/c

n/c

n/c

n/c

n/c

n/c

n/c

n/c

As shown with Belden 9729 color code

Pin 1 - Com

Pin 2 - DMX - (Black)

Pin 3 - DMX + (Red)

DMX In and Pass-Thru on the same pluggable

screw connector as shown.

For use with CAT 5 cable, contact ETC for a

CAT 5 termination and IDC connector kit (ETC

part number 4100A1013), sold separately.