The six position pluggable screw terminal labeled J3 Panic/LON is provided as the
termination point for both Emergency and SmartLink control.
Connect Emergency
Step 1:
Strip 6.35mm (1/4”) of insulation from the ends of the two 1.5mm
2
wires.
Step 2:
Remove the 6 position pluggable connector from J3 on the I/O PCB.
Step 3:
Twist the two 1.5mm
2
wires together as close to the connector as possible.
Step 4:
Insert the 1.5mm
2
into pins 5 and 6.
Step 5:
Tighten the screw firmly onto each wire.
Connect SmartLink
Termination is available for up to two separate SmartLink data runs and is FTT-10A
topology-free and polarity independent utilizing a LonWorks
®
network. For systems utilizing
SmartLink wall stations, ETC recommends terminating the station data run to the
SmartPack with the LinkPower supply installed and utilizing the second data bus for
SmartLink pack to pack synchronization. A clean, well organized wire installation assists
with troubleshooting efforts when needed.
Step 1:
Cut the Belden 8471 cable so that a 20cm (8”) tail extends from the edge of the
panel.
Step 2:
Strip 18cm (7”) of the outer jacket off.
Step 3:
If pulling two Belden 8471 cables, label each pair with data type and run
designation. Example: SL1 and SL2.
Step 4:
Strip 6.35mm (1/4”) of insulation from the ends of the Belden 8471 wires.
Step 5:
Insert the white wire from SL1 data run into pin 1 (NETB) terminal on the
pluggable connector. Tighten the screw firmly onto the wire.
Step 6:
Insert the associated SL1 black wire into pin 2 (NETA) terminal on the pluggable
connector. Tighten the screw firmly onto the wire.
Step 7:
Repeat steps 5-6 to terminate the second data run (SL2) if required to the
remaining pins 3 and 4 terminals on the connector. Tighten the screw firmly onto
each wire.
Step 8:
Reinstall the 6 position pluggable connector to J3 on the I/O PCB.
N o t e :
One SmartLink host product (SmartPack, SmartSwitch, Unison DRd with
SmartLink or Sensor + with SmartLink) in the system must have a LinkPower
Supply or Station Power Module installed for wall station power. A SmartLink
LinkPower supply (7021K1010) is limited to powering four SmartLink stations.
Alternatively, you may power up to 16 SmartLink stations when using a SmartLink
Station Power Module (S-SPM). You may have up to four SmartLink host products
in a SmartLink system.
NETB
NET
A
NETB
NET
A
COM
PA
N
1 2 3 4 5 6
COM
Emergency
NET
A
NET
B
NET
B
NET
A
LON1
LON2
DMX
NC
J2
Control
1 2 3 4