Masts – ERICO 3000 ERITECH SYSTEM User Manual
Page 9

INSTALLATION, OPERATION AND MAINTENANCE MANUAL
7
www.erico.com
Masts
There are three main types of mast 
configurations:
t
Guyed - generally required for mast
heights of over 3 m (10 ft) or for 
climatic conditions where wind gusts 
may exceed 160 km/h (100 mph). 
Always consult with a local civil 
engineer if in doubt. The mast is 
anchored at the base and then guyed 
using one or two guy sets, depending 
on the mast height and configuration, 
each with 3 lengths of non conductive 
guying material. 
t
Cantilevered - the lower third of the
mast is secured to a vertical surface 
to provide support. These may also 
require guying depending on mast 
height.
t
Free-standing - base support only.
Ensure that the configurations and 
heights for your specific installation 
conform to the design and consultation 
directives.
Specific advice for each mast configur-
ation is provided on pages 40 to 47.
When all of the components for the 
ERITECH
®
SYSTEM 3000 have been
received, they should be checked against 
the design “Bill of Materials” and for any 
possible shipping loss or damage.
Ensure the air terminal is supplied with the 
finial tip secured in place. The air terminal 
is supplied with three different finial tip 
configurations (two separate, and one 
secured in place), similar to that shown 
in photo 1. It is important that the 
correct finial tip is installed, specific 
to the application. Photo 2 shows the 
three different finial tip sizes, ranging from 
sharp to blunt in dimension. The sharp tip 
(middle), medium tip (left) and rounded tip 
(right). The application of each of these tips 
is detailed below:
t
Sharp Tip – Terminal heights less than
20 m (65 ft)
t
Medium Tip – Terminal heights less
than 50 m (165 ft), greater than 20 m 
(65 ft)
t
Rounded Tip – Terminal heights greater
than 50 m (165 ft)
Note: heights listed refer to the actual terminal height above ground
level
If required, replace the finial tip supplied 
with the appropriate tip for the application, 
and tighten firmly. 
Warning – Do not install the ERITECH
®
DYNASPHERE without installing the 
correct finial tip.
1 – ERITECH DYNASPHERE with two spare finial tips.
2 – Three (3) ERITECH DYNASPHERE finial tip sizes.