ERICO 3000 ERITECH SYSTEM User Manual
Page 39

INSTALLATION, OPERATION AND MAINTENANCE MANUAL
37
www.erico.com
Photo 11: Installed compression coupling.
The coupling must be tightened 
using spanners / wrenches, as 
tightning by hands will not be 
adequate.
22. Using the roll of silicone tape (grey), 
overwrap half layers from 20 mm (
3
⁄
4
in.) over
the end of the coldshrink to 30 mm (1
1
⁄
8
in.)
over the coupling so that it covers the joint 
between the main coupling and compression 
nut, (refer to figure 24 on page 39).
Wrap with moderate tension (10 to 100% 
stretch). Apply one final layer with no stretch. 
Press down, to avoid the end lifting before 
fusion of the tape takes place.
 The finished termination must be 
protected against any abrasion 
and sharp edges during transport 
or installation, as the coldshrink 
tubes are susceptible to ripping or 
tearing if nicked or scuffed.
23. The structure bonding braid MUST be 
electrically connected via a 6 mm
2
(8 AWG)
length of insulated copper cable to the 
specified conductive structural point, as 
described in the ERITECH
®
SYSTEM 3000
Installation, Operation & Maintenance 
Manual.
Connecting the ERITECH
®
DYNASPHERE
24. Feed the downconductor (and 
structure bonding cable) through the 
FRP mast so that the entire termination 
is protruding from the top of the mast. 
Remove the lock screw in the base of the 
ERITECH
®
DYNASPHERE terminal, then
screw the terminal all the way onto the 
termination coupling thread. Replace the 
lock screw back into position so that it 
locks the thread into place and will stop 
the terminal from unscrewing.
25. Carefully pull the downconductor 
(and structure bonding cable) back down 
through the FRP mast so that the terminal 
base sits correctly in the top of the mast. 
Twist the FRP mast at least one complete 
turn at the base of the terminal to remove 
any stress on the termination sheds 
(flanges) and to seat the terminal correctly. 
