beautypg.com

ERICO CADDY PYRAMID TF Series, Fixed Height Tool-Free Supports User Manual

Caddy pyramid tf series, Fixed height tool-free supports

background image

Use Any Combination

of Small Holes

*Maximum recommended load at 10.6 psi [73 kpa] roof loading. Contact project or roofing

engineer for maximum allowable load on individual project roof system.

*All loads are assumed to be uniformly distributed.
ERICO does not recommend the use of CADDY PYRAMID TF series supports on sloped

rooftops with more than 1/12 pitch unless there is a structural attachment of the supports

to the roof structure.

R

Installation steps:

Sweep off loose gravel, if gravel exists.

1.

Consult manufacturer of existing or new roofing system to

2.

determine what type of isolation pads are required by their

roofing system.

3. After pads are installed, place bases on pads.

4. Place pipe in desired location on support.

5. Push clamp down through top holes for pipe retention.

1: Align Pipe

and Clamp

2: Push Down Clamp

Against Pipe

Part Number

Article

Number

Description

Pipe OD Range

Max. Number

Clamps

Max. Rec.

Load*

in[mm]

PTF1C PTF2C

LBF[N]

PTF6

360460

Fixed Height Tool-Free Support: 4 In.[101mm] Tall, 5.5 In.[139mm] Long

-

3

1

300[1334]

PTF10

360461

Fixed Height Tool-Free Support: 4 In.[101mm] Tall, 10 In.[254mm] Long

-

5

2

1000[4450]

PTF16

360462

Fixed Height Tool-Free Support: 4 In.[101mm] Tall, 16 In.[406mm] Long

-

7

3

1500[6670]

PTF1C

360484

Tool-Free Rooftop Pipe Clamp: 3/8" - 1" NPS Pipe [10-25 DN Pipe]

0.50[12.7]-1.32[33.4]

-

-

-

PTF2C

360485

Tool-Free Rooftop Pipe Clamp: 1" - 2" NPS Pipe [15-50 DN Pipe]

0.84[21.3]-2.38[60.3]

-

-

-

TECHNICAL SUPPORT:

www.erico.com

CFS487_A

INSTRUCTION SHEET

1 OF 2

© 2014 ERICO International Corporation.

CADDY PYRAMID TF Series

Fixed Height Tool-Free Supports

WARNING:

ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at

1.

www.erico.com and from your ERICO customer service representative.

ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.

2.

All instructions must be completely followed to ensure proper and safe installation and performance.

3.

Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property

4.

damage, serious bodily injury and death.

Products that are manufactured using spring steel components shall be used only in a non-corrosive indoor environment.

5.

All pipe supports, hangers, intermediate components and structural attachments must ONLY be used as described herein and are NEVER to be used for any

6.

other purpose.

NOTE: All load ratings are for static conditions and do not account for dynamic loading such as wind, water or seismic loads, unless otherwise noted.
The customer is responsible for:

a. Conformance to all governing codes.

b. The integrity of structures to which the products are attached, including their capability of safely accepting the loads imposed, as evaluated by a qualified

engineer.

c. Using appropriate industry standard hardware as noted above.
SAFETY INSTRUCTIONS:

All governing codes and regulations and those required by the job site must be observed.

Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.

CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.

R